    For use on non-armoured/braided cables.

    Ex e (8161/5 black) and Ex i (8161/6 black/blue) versions. Certified for use in "increased Safety" type enclosures - version with blue cap nut is available.
    As single or multi-cable entry (only M25 and M32).
    Integrated plug (must be ordered separately) for closing unused cable entries
    Cable diameter ranges from 4 mm up to 48 mm

    Utskriftvennlig versjon
  • 8161 Plastic - EEx e/EEx i
    Ex protection Increased Safety Exe
    Protection code II 2 GD
    ATEX certificate PTB 00 ATEX 3119 X
    IECEx certificate IECEx PTB 05.0016 X
    Zone Zone 1, Zone 2, Zone 21 and Zone 22
    Gas group Ex e II
    Standards 60079-0 and 60079-7
    Operating temp. -40°C to +75°C
    Igress protection IP66 and IP68 (6 bar for 1 day)
    Impact strength 7 J
    Material Polyamide
    Armour clamping No
    Sealing Cable outher sheath 